AH-031: Series Detectors

A H – 0 3 1 :   S E R I E S   D E T E C T O R S

AH-0311AH-0311-B

AH-0311

MULTI-PURPOSE SMOKE DETECTOR

 

Characteristics

  • Special chamber design has greatly decreased dust levels and improved detection accuracy.
  • Dual LEDs for 360-degree visibility.
  • Advanced technology enables this detector to increase its precision in fire detection, improve signals to avoid noise interference and thus reduce unwanted false alarm.
  • Low current consumption that allows more detectors to be used with each control panel.
  • Dual contacts on the base which enhance the connecting stability between sensor and base.
  • All bases are fitted with a shorting spring to permit maintenance without disconnecting when removing the detector head.

Multi-purpose Resettable Type

This unit has designed for relay output feature with optional individual power source and it has been used widely in the current market. This resettable detector is not only use as a fire alarm system but will also supervise input power via an optional relay output for power breakdown or wire break. Fault relay contact will open when power breakdown occur and fire alarm signal will transmitted to connected system or computer terminal when detector is activated. When the alarm signal is absent the detector will automatically return to standby status. Optional built-in buzzer can sound a warning at the first sign of fire. This detector is currently used quite often in security systems and is also promoted for use in communications, banking, shipping or the art business.

Specifications

Model

AH-0311-2

AH-0311-3

AH-0311-4

Voltage Range

12 ~ 30V DC

Standby Current

35μA

Alarm Current
@24V DC 470Ω 

40mA

30mA

40mA

Sensitivity Setting

Comply to EN54

Ambient Temperature

-10°C ~ +55°C

Material

Fire-proof plastic

Dimensions

102mm(Dia.) x 49mm(H)

Weight

155g

157g

165g

Color

White

 

Order information

AH-0311-2 2-wire
AH-0311-3 3-wire with remote indicator output
AH-0311-4 4-wire with relay output 

 

Specifications (Resettable)

Model

AH-0311-S

AH-0311-BS

AH-0311-BPS

Alarm Current

15mA

50mA

80mA

Standby Current

115µA

115µA

15mA

Voltage Range

12V DC

12V DC

12V DC

Weight

168g

170g

170g

 

Order Information (Resettable)

AH-0311-S + Relay Output
AH-0311-BS + Buzzer + Relay Output
AH-0311-BPS + Buzzer + Power off & Wire Disconnection Warning + Relay Output

 

Effective alert area

Building Height Area Covered
Under 4M 150M2
4 ~ 20M 75M2

 


AH-0315-AAH-0315-B

AH-0315

MULTI-PURPOSE SMOKE AND HEAT DETECTOR

 

Characteristics

  • Special chamber design has greatly decreased dust levels and improved detection accuracy.
  • Dual LEDs for 360-degree visibility.
  • Advanced technology enables this detector to increase its precision in fire detection, improve signals to avoid noise interference and thus reduce unwanted false alarm.
  • Low current consumption that allows more detectors to be used with each control panel.
  • Dual contacts on the base which enhance the connecting stability between sensor and base.
  • All bases are fitted with a shorting spring to permit maintenance without disconnecting when removing the detector head.

Multi-purpose Resettable Type

This unit has designed for relay output feature with optional individual power source and it has been used widely in the current market. This resettable detector is not only use as a fire alarm system but will also supervise input power via an optional relay output for power breakdown or wire break. Fault relay contact will open when power breakdown occur and fire alarm signal will transmitted to connected system or computer terminal when detector is activated. When the alarm signal is absent the detector will automatically return to standby status. Optional built-in buzzer can sound a warning at the first sign of fire. This detector is currently used quite often in security systems and is also promoted for use in communications, banking, shipping or the art business.

Specifications

Model

AH-0315-2

AH-0315-3

AH-0315-4

Voltage Range

12 ~ 30V DC

Standby Current

55μA

Alarm Current
@24V DC 470Ω

40mA

30mA

40mA

Sensitivity Setting

Comply to EN54

Thermal Setting

58℃

Response Grade

Comply to EN54, Grade 1

Ambient Temperature

-10℃ ~ +55℃

Material

Fire-proof plastic

Dimensions

102mm(Dia.) x58mm(H)

Weight

155g

157g

165g

Color

White

 

Order information

AH-0315-2 2-wire
AH-0315-3 3-wire with remote indicator output
AH-0315-4 4-wire with relay output

 

Specifications (Resettable)

Model

AH-0315-S

AH-0315-BS

AH-0315-BPS

Alarm Current

25mA

65mA

80mA

Standby Current

125μA

125μA

15mA

Voltage Range

12V DC

12V DC

12V DC

Weight

164g

166g

171g

 

Order Information (Resettable)

AH-0315-S + Relay Output
AH-0315-BS + Buzzer + Relay Output
AH-0315-BPS + Buzzer + Power off & Wire
Disconnection Warning + Relay Output

 

Effective alert area

Building Height Area Covered
Under 4M 150 M2
4 ~ 20M 75 M2

AH-0316-AAH-0316-B

AH-0316

MULTI-PURPOSE COMBINATION HEAT DETECTOR

 

Characteristics

  • Special chamber design has greatly decreased dust levels and improved detection accuracy.
  • Dual LEDs for 360-degree visibility.
  • Advanced technology enables this detector to increase its precision in fire detection, improve signals to avoid noise interference and thus reduce unwanted false alarm.
  • Low current consumption that allows more detectors to be used with each control panel.
  • Dual contacts on the base which enhance the connecting stability between sensor and base.
  • All bases are fitted with a shorting spring to permit maintenance without disconnecting when removing the detector head.

Multi-purpose Resettable Type

This unit has designed for relay output feature with optional individual power source and it has been used widely in the current market. This resettable detector is not only use as a fire alarm system but will also supervise input power via an optional relay output for power breakdown or wire break. Fault relay contact will open when power breakdown occur and fire alarm signal will transmitted to connected system or computer terminal when detector is activated. When the alarm signal is absent the detector will automatically return to standby status. Optional built-in buzzer can sound a warning at the first sign of fire. This detector is currently used quite often in security systems and is also promoted for use in communications, banking, shipping or the art business.

Specifications

Model

AH-0316-2

AH-0316-3

AH-0316-4

Voltage Range

12 ~ 30V DC

Standby Current

45μA

 

     
Alarm Current
@24V DC 470Ω

30mA

35mA

40mA

Thermal Setting

58℃

Response Grade

Comply to EN54, Grade 1

Ambient Temperature

-10℃ ~ +55℃

Material

Fire-proof plastic

Dimensions

102mm(Dia.) x58mm(H)

Weight

145g

147g

160g

Color

White

 

Order information

AH-0316-2 2-wire
AH-0316-3 3-wire with remote indicator output
AH-0316-4 4-wire with relay output

 

Specifications (Resettable)

Model AH-0316-S
Alarm Current 35mA
Standby Current 30μA
Voltage Range 12V DC
Weight 157g

 

Order Information (Resettable)

AH-0316-S + Relay Output

 

Effective alert area

Construction/Height

Under 4M

4M ~ 8M

Fire-proof Building

90 M2

45 M2

Ordinary Building

50 M2

30 M2

 

 